Funiculus fasciculatus aërius ABC secundum normam MV AS/NZS 3599

Funiculus fasciculatus aërius ABC secundum normam MV AS/NZS 3599

Specificationes:

    AS/NZS 3599 est series normarum pro funibus aeriis fasciculatis (ABC) mediae tensionis (MV) in retibus distributionis aereae adhibitis.
    AS/NZS 3599—Funes electrici—Fasciculi aerei—Insulati polymerice—Tensiones 6.3511 (12) kV et 12.722 (24) kV
    AS/NZS 3599 requisita designandi, constructionis, et probationis horum funium specificat, sectionibus diversis pro funibus blindatis et non blindatis inclusis.

Brevis Detalia

Tabula Parametrorum

Applicatio:

Funes aerei mediae tensionis fasciculati imprimis adhibentur adlineae aereae secundariaein perticis vel ut alimentatores ad aedificia residentialia.

asd
asd

Norma:

AS/NZS 3599 --- Funes electrici — Aerei fasciculati — Polymericis insulati — Tensiones 6.3511 (12) kV et 12.722 (24) kV

Tensio electrica:

6.6kV-22kV

Constructio:

Tegumentum Conductorium: Stratum semiconductivum extrusum.
Insulatio: XLPE.
Velum insulationis: Stratum semiconductivum extrusum.
Velum Metallicum (ad libitum): Velum filum cupreum vel velum taeniae cupreae.
Separator: Taenia semiconductiva tumescens.
Involucrum externum: HDPE.
Conductor Adiutor:Fila ferrea galvanizata.
Tres nuclei reticulati, insulati et XLPE, circa fila chalybea galvanizata ordine dextro convolvuntur.

asd

Cur Nos Eligas?

Funes qualitate praestantes, materiis summae qualitatis utentes, producimus:

Cur Nos Eligas (2)
Cur Nos Eligas (3)
Cur Nos Eligas (1)
Cur Nos Eligas (5)
Cur Nos Eligas (4)
Cur Nos Eligas (6)

Turma dives perita sciens quid sit postulatio tua:

1212

Officina cum bonis instrumentis et capacitate ad traditionem tempore praestandam:

1213

Funes non-protecti 6.35/11kV AL/XLPE/HDPE secundum normam AS/NZS 3599 pars 1

Numerus Nucleorum × Sectio Transversa Nominalis

Conductor Phasei

Unitas Suspensionis Nuntii

Area Sectionalis Nominalis

Onus Frangens

Diameter Conductoris

Crassitudo insulationis

Crassitudo Tegimenti Insulationis

Crassitudo Vaginae

Eiectio

Numerus × mm²

mm

mm

mm

mm

Numerus × mm

mm²

kN

3×35 6.9 3.4 0.8 1.2 7/4.75 52.4 1370
3×50 8.1 3.4 0.8 1.2 7/4.75 54.6 MDXXX
3×70 9.7 3.4 0.8 1.2 7/4.75 57.8 MDCCXC
3×95 11.4 3.4 0.8 1.2 7/4.75 61.3 2100
3×120 12.8 3.4 0.8 1.2 19/3.50 67.3 2540
3×150 14.2 3.4 0.8 1.2 19/3.50 70.1 2840
3×185 15.7 3.4 0.8 1.2 19/3.50 73.1 3190

 

Funes obtecti 6.35/11kV AL/XLPE/CWS/HDPE secundum normam AS/ZNS 3599 pars 1

Numerus Nucleorum × Sectio Transversa Nominalis

Diameter Conductoris

Crassitudo insulationis

Crassitudo Tegimenti Insulationis

Filum Cupreum Tegmen Stranding

Crassitudo Vaginae

Filum Ferreum Galvanizatum Stranding

Area Sectionalis Nominalis

Onus Frangens

Numerus × mm²

mm

mm

mm

Numerus × mm

mm

Numerus × mm

mm²

kN

Velum leve
3×35 6.9 3.4 0.8 25/0.85 1.8 7/2.00 54.1 MDCCCXX
3×35 6.9 3.4 0.8 25/0.85 1.8 19/2.00 58.1 2130
3×50 8.1 3.4 0.8 25/0.85 1.8 19/2.00 60.4 2300
3×70 9.7 3.4 0.8 25/0.85 1.8 19/2.00 63.6 2570
3×95 11.4 3.4 0.8 25/0.85 1.8 19/2.00 67.0 2900
3×120 12.8 3.4 0.8 25/0.85 1.8 19/2.00 69.8 3190
3×150 14.2 3.4 0.8 25/0.85 1.9 19/2.00 73.0 3530
3×185 15.7 3.4 0.8 25/0.85 1.9 19/2.00 76.0 3890
Velum grave
3×35 6.9 3.4 0.8 40/0.85 1.8 7/2.00 54.1 2050
3×35 6.9 3.4 0.8 40/0.85 1.8 19/2.00 58.1 2360
3×50 8.1 3.4 0.8 XXIII/I.XXXV 1.8 19/2.00 62.4 2820
3×70 9.7 3.4 0.8 32/1.35 1.8 19/2.00 65.6 3440
3×95 11.4 3.4 0.8 39/1.35 1.8 19/2.00 69.0 4030
3×120 12.8 3.4 0.8 39/1.35 1.8 19/2.00 71.8 4320
3×150 14.2 3.4 0.8 39/1.35 1.9 19/2.00 75.0 4670
3×185 15.7 3.4 0.8 39/1.35 1.9 19/2.00 78.0 5020

 

Funes non-protecti 12.7/22kV AL/XLPE/HDPE secundum normam AS/NZS 3599 pars 1

Numerus Nucleorum × Sectio Transversa Nominalis

Conductor Phasei

Unitas Suspensionis Nuntii

Area Sectionalis Nominalis

Onus Frangens

Diameter Conductoris

Crassitudo insulationis

Crassitudo Tegimenti Insulationis

Crassitudo Vaginae

Eiectio

Numerus × mm²

mm

mm

mm

mm

Numerus × mm

mm²

kN

3×35 6.9 5.5 0.8 1.2 7/4.75 61.0 MDCCLXXX
3×50 8.1 5.5 0.8 1.2 7/4.75 63.3 MCMLXX
3×70 9.7 5.5 0.8 1.2 7/4.75 66.5 2260
3×95 11.4 5.5 0.8 1.2 7/4.75 69.9 2600
3×120 12.8 5.5 0.8 1.2 19/3.50 75.9 3070
3×150 14.2 5.5 0.8 1.2 19/3.50 78.7 3390
3×185 15.7 5.5 0.8 1.2 19/3.50 81.7 3760

 

Funes obtecti 12.7/22kV AL/XLPE/CW/HDPE secundum normam AS/NZS 3599 pars 1

Numerus Nucleorum × Sectio Transversa Nominalis

Diameter Conductoris

Crassitudo insulationis

Crassitudo Tegimenti Insulationis

Filum Cupreum Tegmen Stranding

Crassitudo Vaginae

Filum Ferreum Galvanizatum Stranding

Area Sectionalis Nominalis

Onus Frangens

Numerus × mm²

mm

mm

mm

Numerus × mm

mm

Numerus × mm

mm²

kN

Velum leve
3×35 6.9 5.5 0.8 25/0.85 1.8 7/2.00 62.7 2280
3×35 6.9 5.5 0.8 25/0.85 1.8 19/2.00 66.7 2580
3×50 8.1 5.5 0.8 25/0.85 1.8 19/2.00 69.0 2780
3×70 9.7 5.5 0.8 25/0.85 1.9 19/2.00 72.6 3110
3×95 11.4 5.5 0.8 25/0.85 1.9 19/2.00 76.0 3460
3×120 12.8 5.5 0.8 25/0.85 2.0 19/2.00 79.2 3810
3×150 14.2 5.5 1.0 25/0.85 2.0 19/2.00 82.8 4230
3×185 15.7 5.5 1.0 25/0.85 2.1 19/2.00 86.2 4650
Velum grave
3×35 6.9 5.5 0.8 40/0.85 1.8 7/2.00 62.7 2510
3×35 6.9 5.5 0.8 40/0.85 1.8 19/2.00 66.7 2810
3×50 8.1 5.5 0.8 XXIII/I.XXXV 1.8 19/2.00 71.0 3300
3×70 9.7 5.5 0.8 32/1.35 1.9 19/2.00 74.6 3970
3×95 11.4 5.5 0.8 39/1.35 1.9 19/2.00 78.0 4600
3×120 12.8 5.5 0.8 39/1.35 2.0 19/2.00 81.2 4950
3×150 14.2 5.5 1.0 39/1.35 2.0 19/2.00 84.8 5360
3×185 15.7 5.5 1.0 39/1.35 2.1 19/2.00 88.2 5790

 Data technica

Sectio Transversa Nominalis

Aestimatio Currentis Continui

Aer Tranquillus

Ventus 1m/s

Ventus 2m/s

mm² A A A
35 105 145 CLXV
50 125 CLXX ducenti
70 CL 215 250
95 CLXXX 260 trecenti
CXX 205 trecenti 350
CL 230 340 395
CLXXXV 265 390 450