AS/NZS 3599--- Funes Electrici — Aerei Fasciculi— Polymericae insulatae—Voltages 6.3511 (12) kV et 12.722 (24) kV
6.6kV-22kV
Conductor Screen: Extruded semi-conductive layer.
Insulatio: XLPE.
Insulation Screen:
Screen metallicum (libitum): Velum filum cupreum vel taenia taeniola aenea.
Separator: machinae magneticae semi-conductivae.
Exterior Vagina: HDPE.
Support Conductor:Fila ferro Galvanized.
Conventus Tres XLPE nuclei insulatae nuclei tegentes inter fila ferrea galvanizata in dextra manu iacebant.
Quales rudentes efficimus utendo materia summus finis;
Dives usus bigas sciens quid petis:
Planta cum bonis facultatibus et capacitatibus praestandi in tempore partus;
AS/NZS 3599 part 1 6.35/11kV AL/XLPE/HDPE funes non obiectu
Numerus Cores x Nominal Cross Section | Phase Conductor | Nuntius Suspensionis Unit | Nominal Area | Fractio Load | |||
Diameter Conductor | Crassitudo Insulation | Crassitudo Insulation 'collaborative | Crassitudo Vagina | Stranding | |||
No.×mm² | mm | mm | mm | mm | No.×mm | mm² | kN |
3×35 | 6.9 | 3.4 | 0.8 | 1.2 | 7/4.75 | 52.4 | 1370 |
3×50 | 8.1 | 3.4 | 0.8 | 1.2 | 7/4.75 | 54.6 | 1530 |
3×70 | 9.7 | 3.4 | 0.8 | 1.2 | 7/4.75 | 57.8 | 1790 |
3×95 | 11.4 | 3.4 | 0.8 | 1.2 | 7/4.75 | 61.3 | 2100 |
3×120 | 12.8 | 3.4 | 0.8 | 1.2 | 19/3.50 | 67.3 | 2540 |
3×150 | 14.2 | 3.4 | 0.8 | 1.2 | 19/3.50 | 70.1 | 2840 |
3× 185 | 15.7 | 3.4 | 0.8 | 1.2 | 19/3.50 | 73.1 | 3190 |
AS/ZNS 3599 part 1 6.35/11kV AL/XLPE/CWS/HDPE retinacula obducta
Numerus Cores x Nominal Cross Section | Diameter Conductor | Crassitudo Insulation | Crassitudo Insulation 'collaborative | Filum aeris Screen Stranding | Crassitudo Vagina | Galvanized Steel Wire Stranding | Nominal Area | Fractio Load |
No.×mm² | mm | mm | mm | No.×mm | mm | No.×mm | mm² | kN |
Lux officium screen | ||||||||
3×35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 54.1 | 1820 |
3×35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 58.1 | 2130 |
3×50 | 8.1 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 60.4 | 2300 |
3×70 | 9.7 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 63.6 | 2570 |
3×95 | 11.4 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 67.0 | 2900 |
3×120 | 12.8 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.8 | 3190 |
3×150 | 14.2 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 73.0 | 3530 |
3× 185 | 15.7 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 76.0 | 3890 |
Gravis officium screen | ||||||||
3×35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 54.1 | 2050 |
3×35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 58.1 | 2360 |
3×50 | 8.1 | 3.4 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 62.4 | 2820 |
3×70 | 9.7 | 3.4 | 0.8 | 32/1.35 | 1.8 | 19/2.00 | 65.6 | 3440 |
3×95 | 11.4 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 69.0 | 4030 |
3×120 | 12.8 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 71.8 | 4320 |
3×150 | 14.2 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 75.0 | 4670 |
3× 185 | 15.7 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 5020 |
AS/NZS 3599 part 1 12.7/22kV AL/XLPE/HDPE funes non obiectu
Numerus Cores x Nominal Cross Section | Phase Conductor | Nuntius Suspensionis Unit | Nominal Area | Fractio Load | |||
Diameter Conductor | Crassitudo Insulation | Crassitudo Insulation 'collaborative | Crassitudo Vagina | Stranding | |||
No.×mm² | mm | mm | mm | mm | No.×mm | mm² | kN |
3×35 | 6.9 | 5.5 | 0.8 | 1.2 | 7/4.75 | 61.0 | 1780 |
3×50 | 8.1 | 5.5 | 0.8 | 1.2 | 7/4.75 | 63.3 | 1970 |
3×70 | 9.7 | 5.5 | 0.8 | 1.2 | 7/4.75 | 66.5 | 2260 |
3×95 | 11.4 | 5.5 | 0.8 | 1.2 | 7/4.75 | 69.9 | 2600 |
3×120 | 12.8 | 5.5 | 0.8 | 1.2 | 19/3.50 | 75.9 | 3070 |
3×150 | 14.2 | 5.5 | 0.8 | 1.2 | 19/3.50 | 78.7 | 3390 |
3× 185 | 15.7 | 5.5 | 0.8 | 1.2 | 19/3.50 | 81.7 | 3760 |
AS/NZS 3599 part 1 12.7/22kV AL/XLPE/CW/HDPE retinacula obducta
Numerus Cores x Nominal Cross Section | Diameter Conductor | Crassitudo Insulation | Crassitudo Insulation 'collaborative | Filum aeris Screen Stranding | Crassitudo Vagina | Galvanized Steel Wire Stranding | Nominal Area | Fractio Load |
No.×mm² | mm | mm | mm | No.×mm | mm | No.×mm | mm² | kN |
Lux officium screen | ||||||||
3×35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 62.7 | 2280 |
3×35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 66.7 | 2580 |
3×50 | 8.1 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.0 | 2780 |
3×70 | 9.7 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 72.6 | 3110 |
3×95 | 11.4 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 76.0 | 3460 |
3×120 | 12.8 | 5.5 | 0.8 | 25/0.85 | 2.0 | 19/2.00 | 79.2 | 3810 |
3×150 | 14.2 | 5.5 | 1.0 | 25/0.85 | 2.0 | 19/2.00 | 82.8 | 4230 |
3× 185 | 15.7 | 5.5 | 1.0 | 25/0.85 | 2.1 | 19/2.00 | 86.2 | 4650 |
Gravis officium screen | ||||||||
3×35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 62.7 | 2510 |
3×35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 66.7 | 2810 |
3×50 | 8.1 | 5.5 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 71.0 | 3300 |
3×70 | 9.7 | 5.5 | 0.8 | 32/1.35 | 1.9 | 19/2.00 | 74.6 | 3970 |
3×95 | 11.4 | 5.5 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 4600 |
3×120 | 12.8 | 5.5 | 0.8 | 39/1.35 | 2.0 | 19/2.00 | 81.2 | 4950 |
3×150 | 14.2 | 5.5 | 1.0 | 39/1.35 | 2.0 | 19/2.00 | 84.8 | 5360 |
3× 185 | 15.7 | 5.5 | 1.0 | 39/1.35 | 2.1 | 19/2.00 | 88.2 | 5790 |
Technical data
Nominal Cross Section | Continua Current Rating | ||
adhuc Air | 1m / s venti | 2m/s ventus | |
mm² | A | A | A |
35 | 105 | 145 | 165 |
50 | 125 | 170 | 200 |
70 | 150 | 215 | 250 |
95 | 180 | 260 | 300 |
120 | 205 | 300 | 350 |
150 | 230 | 340 | 395 |
185 | 265 | 390 | 450 |