Idoneum retibus energiae, ut stationibus electricis. Ad institutionem in canalibus, subterraneis et extra aedes. Nota bene: Involucrum externum rubrum, radiis ultraviolaceae expositum, decolorari potest.
Idoneum retibus energiae, ut stationibus electricis. Ad institutionem in canalibus, subterraneis et extra aedes. Nota bene: Involucrum externum rubrum, radiis ultraviolaceae expositum, decolorari potest.
Propagatio flammae secundum BS EN60332
BS6622
IEC 60502
Conductor: conductores cuprei compacti circulares, simplex et recocti, velconductor aluminii
Insulatio: polyethylene reticulatum (XLPE)
Velum Metallicum: velum cupreum singulare vel totum
Separator: taenia cuprea cum 10% imbricatione
Stragula: polyvinylchloridum (PVC)
Armamenta: Armamenta Fili Ferrei (SWA), Armamenta Taeniae Ferreae (STA), Armamenta Fili Aluminei (AWA), Armamenta Taeniae Aluminei (ATA)
Vagina: vagina externa PVC
Color vaginae: Ruber vel Niger
Temperatura maxima operationis conductoris: 90°C
Temperatura maxima operationis scrinii: 80°C
Temperatura maxima conductoris per SC: 250°C
Conditiones depositionis ad formationem trifolii sunt hae:
Resistivitas thermalis soli: 120°C. cm/Watt
Profunditas sepulturae: 0.5m
Temperatura soli: 15°C
Temperatura aeris: 25°C
Frequentia: 50Hz
Area nominalis conductoris | Diameter conductoris | Crassitudo insulationis | Diameter nominalis totalis | Diameter maximus totius | Pondus funis approximatum kg/km | Radius flexionis minimus | |
mm² | mm | mm | mm | mm | Cu | Al | mm |
1x 25 | 6.0 | 5.5 | 26.0 | 27.0 | DCCCXCII | DCCXXXVII | 380 |
1x 35 | 7.0 | 5.5 | 27.1 | 28.1 | 1021 | 804 | 390 |
1x 50 | 8.2 | 5.5 | 28.5 | 29.5 | 1216 | 902 | 410 |
1x 70 | 9.9 | 5.5 | 30.2 | 31.2 | 1464 | 1024 | 440 |
1x 95 | 11.5 | 5.5 | 32.0 | 33.0 | MDCCLXIX | 1171 | 460 |
1×120 | 12.9 | 5.5 | 33.4 | 34.4 | 2052 | 1297 | 480 |
1×150 | 14.2 | 5.5 | 34.9 | 35.9 | 2391 | 1447 | quingenti |
1×185 | 16.2 | 5.5 | 37.1 | 38.1 | 2805 | 1640 | 530 |
1×240 | 18.2 | 5.5 | 39.1 | 40.1 | 3381 | MDCCCLXX | 560 |
1×300 | 21.2 | 5.5 | 42.3 | 43.3 | 4065 | 2176 | DC |
1×400 | 23.4 | 5.5 | 44.7 | 45.7 | 5077 | 2553 | DCXL |
1×500 | 27.3 | 5.5 | 48.8 | 49.8 | 6166 | 3017 | DCC |
1×630 | 30.5 | 5.5 | 52.4 | 53.4 | 7526 | 3559 | DCCCL |
Area nominalis conductoris | Diameter conductoris | Crassitudo insulationis | Diameter nominalis totalis | Diameter maximus totius | Pondus funis approximatum kg/km | Radius flexionis minimus | |
mm² | mm | mm | mm | mm | Cu | Al | mm |
3x 25 | 6.0 | 5.5 | 52.4 | 53.4 | 3611 | 3146 | DCCCL |
3x 35 | 7.0 | 5.5 | 54.5 | 55.5 | 4083 | 3432 | DCCCLXX |
3x 50 | 8.2 | 5.5 | 57.4 | 58.4 | 4771 | 3826 | DCCCX |
3x 70 | 9.9 | 5.5 | 61.2 | 62.2 | 5714 | 4392 | DCCCLXX |
3x 95 | 11.5 | 5.5 | 65.0 | 66.0 | 6810 | 5015 | 920 |
3×120 | 12.9 | 5.5 | 68.2 | 69.2 | 7847 | 5580 | 970 |
3×150 | 14.2 | 5.5 | 71.2 | 72.2 | 9000 | 6166 | 1010 |
3×185 | 16.2 | 5.5 | 75.6 | 76.6 | 10481 | 6986 | 1070 |
3×240 | 18.2 | 5.5 | 80.5 | 82.0 | 12700 | 8200 | 1140 |
Area nominalis conductoris | Diameter conductoris | Crassitudo insulationis | Diameter nominalis totalis | Diameter maximus totius | Pondus funis approximatum kg/km | Radius flexionis minimus | |
mm² | mm | mm | mm | mm | Cu | Al | mm |
3x 25 | 6.0 | 5.5 | 57.5 | 58.5 | 5045 | 4580 | DCCCXX |
3x 35 | 7.0 | 5.5 | 59.8 | 60.8 | 5630 | 4979 | DCCCL |
3x 50 | 8.2 | 5.5 | 62.7 | 63.7 | 6381 | 5436 | DCCCXC |
3x 70 | 9.9 | 5.5 | 66.5 | 67.5 | 7450 | 6128 | 940 |
3x 95 | 11.5 | 5.5 | 70.1 | 71.1 | 8614 | 6820 | 990 |
3×120 | 12.9 | 5.5 | 73.5 | 74.5 | 9780 | 7513 | 1040 |
3×150 | 14.2 | 5.5 | 76.3 | 77.3 | 10962 | 8128 | 1080 |
3×185 | 16.2 | 5.5 | 80.9 | 81.9 | 12611 | 9116 | 1140 |
3×240 | 18.2 | 5.5 | 85.5 | 86.5 | 14792 | 10258 | 1210 |